When using electrical equipment, there are always potential safety issues. These include motors, cables, and household appliances. One of the key factors in their normal operation is the insulation resistance of the insulating materials. When exposed to heat or moisture, insulation can age, reducing its resistance. This may lead to leakage currents or short circuits, which can be dangerous. To prevent such incidents, it's crucial to regularly measure the insulation resistance of all electrical devices to ensure they meet the required standards.
Common measurements are usually taken at low voltages, but these do not reflect the true resistance under high-voltage conditions. A megohmmeter, also known as an insulation resistance tester, is specifically designed for this purpose. It provides a high-voltage power supply during testing, allowing for accurate readings of insulation resistance, which is typically in the megaohm range. While the megohmmeter is convenient and reliable, improper use can introduce errors into the measurement.
Before using a megohmmeter, certain precautions must be taken to ensure both personal and equipment safety:
- Ensure the device under test is completely powered off, and the ground should be short-circuited. Never perform tests on energized equipment.
- If the device might generate high voltage, eliminate that risk before testing.
- Clean the surface of the object being tested to reduce contact resistance and improve accuracy.
- Check that the megohmmeter is functioning properly by verifying the "0" and "∞" points. Shake the handle to reach rated speed and check the readings when the terminals are shorted and open.
- Place the megohmmeter on a stable surface, away from strong magnetic fields or current-carrying conductors.
Once prepared, proper wiring is essential. The megohmmeter has three terminals: “L†(line), “E†(earth), and “G†(guard). Typically, “L†and “E†are used for measuring insulation between two points. However, if the surface is prone to leakage, the “G†terminal should be connected to shield the surface, preventing leakage current from affecting the reading. This is especially important when testing cables, where high humidity or dirt can cause significant leakage currents.
It's critical to connect “L†and “E†correctly. “L†should be connected to the conductor, while “E†should be grounded to the device casing. If reversed, the measurement will be inaccurate, as leakage current may bypass the shielding effect and distort the results. Additionally, the “E†terminal is less insulated than “L,†so incorrect wiring could lead to parallel resistance and unreliable readings.
In summary, accurate insulation resistance testing requires correct usage of the megohmmeter. Any mistake in handling or wiring can compromise the reliability of the results. Proper procedures and attention to detail are essential to ensure safe and effective testing.
1. It’s best to keep all three copies of the documentation for completeness. Archiving only the final engineering test records may not provide a full picture. At that stage, the grounding resistance of the entire lightning protection system is measured, but without detailed records of each test point, it's hard to determine if there are any connection issues between the lightning rod, down conductor, and foundation grounding.
2. For insulation resistance tests, wires should be tested after threading and joint installation, and after electrical appliances are installed, to avoid damage. Cables, on the other hand, should be tested before and after laying to ensure their integrity throughout the process.